SYSTEM CONFIGURATION (ZONES)
ZONES 2 THROUGH 8
These zones have a 350 milliiecond response and can be assigned to any
zone type. They can be EOLR supervised or closed circuit unsupervised, as
required (program field ‘41 determines whether or not these zones will use
the 1,000 ohm EOLR: Enter [l] in field ‘41 to disable the use of EOLR’s on
zones 2 through 8). If programmed for use with EOLR’s. both closed-circuit
and open-circuit devices can be used with the 1.000 ohm EOLR resistor in
series with the bop at the last device, as shown in A below. If the use of
EOLR’s is disabled (‘41-l), only closed-circuft devices can be used, as
shown in B below.
Note that the maximum resistance per zone is 300 ohms.
T&l
m-2
Dlsgram 2A. ZONES 2-3 EOLR SUPERVISED CONFIGURATION
Dlagmm 28.
ZONES 2-8
CLOSED-CIRCUIT UNSUPERVISED CONFIGURATIONS
,--
ADEMCO’r VISTA XM ShtXES TECHNIGU REFERENCE MANUAL