12
XARDWARE OVERVIEW
- E.
l
4152LMB
4280
4280-8
4208
20WIRE POLLING LOOP DEVICES -
POLLING LOOP MODULE
l
When interfaced with the 4171XT-XM dialer board, polling loop and/or
wifeless zone expansion to 64 zones can be accomplished using RPMs
(Remote Point Modules) and/or the 4280 RF receiver module with
ALERT Ill transmitters.
RF RECEIVER MODULE (63 zones)
200 foot range.
Connected to the 4152LMB via a O-wire polling loop, the 4280 can be
used with up to 63 wireless transmitters (ALERT Ill ). plus a wireless
keypad.
House ID ‘SNIFFER’ Mode to ‘sniff out” all other house ID’s from
neighboring systems in the local area.
Transmitter ‘SNIFFER‘ Mode to ‘sniff out’ any transmitters which are
using your House ID.
Up to two 4280s can be used in a system for redundancy, or to increase
the area of coverage.
Powered directly from the polling loop, or separately from auxiliary power.
NOTE: If two 4280s are used. the second 4280 must be powered from
auxiliary power
,Y---.
RF RECEIVER MODULE (8 zones)
l
200 foot range.
l
Connected to the 4152LMB via a P-wire polling loop, the 4280% can he
used with up to 8 wireless transmitters (ALERT Ill type).
.
House ID ‘SNIFFER” Mode to -sniff out’ all other house ID’s in the local
area.
l
Transmitter ‘SNIFFER’ Mode to ‘sniff out’ any transmitters which are
using your House ID.
l
Up to two 42808s can be used for redundancy, or to increase the area of
coverage.
.
Powered directly from the polling loop, or separately from auxiliary power.
NOTE: If two 4280%~ are used, the second 4280-8 must be powered
from auxiliary power
EIGHT ZONE POLLING LOOP EXPANSION MODULE
l
Connected to the 4152LMB via a P-wire polling bop and is used with up
to 8 hard-wired devices.
l
Set DIP switches to identify 8 zones.
. The first two zones can be either normal or fast response (DIP switch
selectable).
.
All zones are EOLR supervised (first six zones = 4.7K, last two zones =
30K).
l
NOTE: Does not support O-wire smoke detectors.
,-,
ADEMCO’s VISTA XM SERIES TECHNICAL REFERENCE MANUAL
WWW.DIYALARMFORUM.COM