108 SPECIAL VL REQUXREMENTS
: >
UL 1610 GRADE A CENTRAL ._. STATlON,~,MERCANTlLE BURGLARY
c-y
INSTALLATIONS -USING iQNQ.1 RANGE RADIO
.
IMPORTANT!: Requires the use of No. 414OATX Control.
NOTE: Not a UL Listed application.
BELL CONNECTIONS Audible alanns must be provided-by the use of AB12 Bell in Box..The AB12
must be mounted so that it can b;e;l heard dutside the protected area.
INSTALLATION NOTES
1. All wiring between AB12 and 4140ATX must be in conduit, and all
conduit holes (knockouts) on the Control panel shall be used or blocked
from access. (Bee Diagram 38.)
2. Use 12V 4’AH (minimum) Battery.
3. Value of End-of-line resistor is li( ohr& (‘41=0).
4. Entry Delays cannot exceed 60 seconds for UL Commercial Burglary
- Listings.
5. Bell timeout cannot be less than 18 minutes for UL Commercial Burglary
Listings.
6. If 4199WH Dual Point RPM are used, tamper detection in Reid Address
‘24 must be enabted (enter 0).
7. Field ‘16 Confirmation of Arming Ding must be enabled.
8. Field l 18 AC Loss Alarm after 4 hours must &* enabled.
9. Field ‘27 24 Hour Test must be enabled.
10. Op&Close reporting must be enabled. ‘-.