Ground Start Module An optional 675 Ground Start module can be used for installations having
telephone lines which require ground start instead of loop start operation to
obtain dial tone from the telco central office. If used, program field 1*46 must be
set to "0" (factory default) and the 675 Ground Start Module must be connected
to the panel's J7 connector trigger output 1, to auxiliary power, and to the "RING"
side of the telephone line as shown in the diagram below.
Use the following procedure to determine the "RING" side of the telephone line:
a. Connect the "+" lead of a DC voltmeter to earth ground, and the "-" lead to one side
of the telephone line.
b. The wire which reads +50VDC is the "RING" side.
When the panel has a message to transmit to the central station, it will seize the
line, go off hook, and then trigger the 675 module to connect the "RING" side of
the telephone line to earth ground. The panel will cause the module to break the
connection between "RING" and earth ground when a dial tone is obtained.
1 2 3 4 5 6 7 8 9
GRAY
YELLOW
WHITE
RED
GREEN
BROWN
BLUE
BLACK
GROUND
OUT 1
GROUND
OUT 2
GROUND
OUT 3
GROUND
OUT 4
J7 CONNECTOR
IF USED.
1. OUT 1 IS NO LONGER
USABLE FOR OPEN/CLOSE
(SEE FIELD 1*46).
2. OUT 2, 3, 4 CAN STILL BE
USED TO PROVIDE ALARM
STATUS INDICATIONS OR TO
OPERATE A KEYSWITCH
(SEE FIELD *15).
N/U
4142TR CABLE
GROUND START
TRIGGER
BLUE
BLACK
VIOLET
BROWN GREEN
TO TELCO
RING
TO EARTH
GROUND
675
GROUND
START
MODULE
(CUT ORANGE
JUMPER)
TO AUX. POWER
TERM. 7
TO AUX. POWER
TERM. 6
(50mA CURRENT DRAW
Remote Console Sounder
Operation & Wiring
An optional Amseco PAL 328N can be used where it is desired to remote the
sounds produced by the console's built-in piezo sounder for one partition. The
panel will remote all sounds (i.e. alarm, trouble, chime, entry/exit, etc.) produced
by the console's built-in sounder except for the short clicks associated with
console key depression. One application of this feature might be to produce
chime sounds in a location which is distant from the panel's consoles. This can
also be accomplished using relay outputs (see Output Relay section). If used, set
program field 1*46 to "2" to enable the remote console sounder option, and the
Amseco piezo must be connected between the panel's auxiliary power and the
J7 connector trigger output as shown below. In addition, field *15 must be used
to select the partition whose console sounds are to trigger the sounder. Zone 7
must be assigned to be a keyswitch zone (even if keyswitch is not used).
1 2 3 4 5 6 7 8 9
GRAY
YELLOW
WHITE
RED
GREEN
BROWN
BLUE
BLACK
GROUND
OUT 1
GROUND
OUT 2
GROUND
OUT 3
GROUND
OUT 4
J7 CONNECTOR
IF USED.
1. OUT 1 IS NO LONGER
USABLE FOR OPEN/CLOSE
OR GROUND START (SEE
FIELD 1*46).
2. OUT 2, 3, 4 CAN STILL BE
USED TO PROVIDE ALARM
STATUS INDICATIONS OR
TO OPERATE A KEYSWITCH
(SEE FIELD *15).
N/U
4142TR CABLE
BLACK
AMSECO PAL-328N
PIEZO SOUNDER
+
RED
TO AUX POWER +
TERMINAL 6
(10mA CURRENT DRAW)