Using The Test
Mode
Doors and Windows
Motion Detectors
Smoke Detectors
Turn Off Test Mode
Armed System Test
After the installation is completed, the Security System should be thoroughly
tested as follows:
1. With the System in the disarmed state, check that all zones are intact. If
DISARMED - Press * to show faults (Alpha consoles) or NOT READY
(Fixed-word consoles) is displayed, press the [*] key to display the
descriptors of the faulted zone(s). Restore faulted zone(s) if necessary, so
that
***DISARMED***/READY TO ARM (Alpha consoles) or READY (Fixed-
word consoles) is displayed.
2. Enter the security code and press the TEST key. The external sounder (if
used) should
sound for 3 seconds and then turn off (the system is operating
on the back-up battety only at this time).
NOTE 1. The system will not enter the Test mode if the battery voltage is too
low, if the battery is not connected, or if any communication
messages are waiting to be transmitted.
NOTE 2. As a reminder that the system is in the Test
mode, the Console will
sound a single beep
at 15-second intervals if no protection zones are
violated.
NOTE 3. In the Test mode, no alarm reports will be sent to the central station.
Also, the external sounder (if used) will not be activated.
Open and close each protected door and window in turn. Each action should
produce three beeps from the Console. The descriptor for each protection zone
will appear on the Console display.
Walk in front of any interior motion detectors. Listen for three beeps when the
detector senses movement. While it is activated, its descriptor will remain
displayed on the Console. Note that wireless PIRs will have a 3-minute lockout
between transmissions to conserve battery life (remove cover for walk test to
override the 3-minute lock-out).
Follow the test procedure provided by the manufacturer of each smoke deteotor
to ensure that all detectors are operational and are functioning properly.
NOTE: A 2-wire smoke detector display will not clear until the Test mode is
exited.
Enter the security code and press the OFF key.
Important! A message will be sent to the central station during the following
tests. Notify the central station that a test will be in progress.
NOTE: A display of “COMM. FAILURE” (Alpha consoles) or
“FC” (Fixed-Word
consoles) indicates a failure to communicate (no Kissoff by the receiver at the
central station after the maximum number of transmission attempts is tried). If
this occurs, verify that the phone line is connected, the correct report format is
programmed, etc.
1. Arm the system and fault one or more zones. Silence alarm sounder(s) each
time by entering the code and pressing OFF. Check that Entry/Exit delay
zones provide the assigned delay times.
2. Check the keypad-initiated alarms, if programmed in field *05, by pressing the
Panic key pairs [x] & [#], [1] & [*], and/or [3] & [#] or dedicated panic keys A,
B, and C, if present.
If the system has been programmed for audible emergency, the console will
emit
a loud, steady alarm sound. The word ALARM and a descriptor “99” will
be displayed for [*] and [#] (or key B), “95” for [1] and [*] (or key A), “96” for
[3] and [#] (or key C).
Silence the alarm by entering the security code and pressing OFF. If the
system has been programmed for silent panic, there will be no audible alarms
or displays. A report will be sent to the central station, however.
3. Notify the central station that all tests are finished and verify results with them.