Zones 2-8
(Cent)
L
Smoke Detectors ● Supports as many 4-wire smoke detectors as can be
m Zones 2-8
powered (see UL Note on next page).
● Assign zone response type 09 (fire).
● The zones must be configured for EOLR supervision.
● A normally-closed, momentary switch must be
installed in series with the power to the detectors in
order to allow reset of the smoke detectors after an
alarm.
● The detectors must be wired in parallel, with the
EOLR at the last detector for full supervision.
● To supervise power, a System Sensor No. A77-716
EOL Relay Module is recommended.
Compatible Glass Break Detectors
Use detectors that are compatible with the following ratings:
StandbyVoltage: 5VDC- 13.8VDC
StandbyResistance: Greaterthan
20k ohms (equivalent resistance of all detectors in
parallel)
AlarmResistance:
Lessthan 1.1k ohms(seenotebelow)
AlarmCurrent:
2mA-10mA
ResetTime: Lessthan6 seconds
The IEI 735L series detectors have been tested and found to be compatible with these
ratings. Up to 50 IEI 735L detectors, connected in parallel, may be used (the alarm
current provided by this zone is sufficient to support operation of only one detector in
alarmed state). Follow the manufacturer’s recommendations on proper installation.
Detectors which exceed 1.1k ohms in alarm, but maintain a voltage drop in alarm of less
than 3.8 volts can also be used.
Zones 2-8 Advisories
Glass Break ●
Detector
Connections
●
Use of N.O. or N.C. contacts on the same zone may prevent proper glass break
detector operation.
UL NOTE: 4-wire smoke detectors cannot be used in UL installations.
When using glass break detectors on zone 6, Address 1*57 must be set to”1”
or “3. Note that the burglary trigger output is no longer available when glass
break detectors are used.
Pin 6 on TB2 (output trigger connector) must be connected to the high side of
zone 6 (terminal 17 on the main terminal block TB1), as shown below.
6
Q
4120XM
TS2 HEAOER
-12-