DESCRIPTION OF 4120XM PROGRAMMING FIELDS
To enter Program Mode, enter Installer code+ [8]+ [0]+ [0].
To set Standard Defaults, press 97.
To access second page of fields, press *94.
To return to first page of fields,
press 99.
To exit Program Mode, press 99 or *98. *99 allows re-entry to Program Mode by installer code. *98 prevents re-
entry to Program
Mode by installer code.
Note that system defau/t values, if not stated in text, are shown underlined.
*OO Installer Code
Enter the 4-digit installer code, which is
the code reserved for installation
(0000-9999)
company use, but can be used by the customer if needed. This is the only code
that can be used to enter the Program mode from the console. This code cannot
be used to enter secondary codes, and cannot be used to disarm the system if
not used to arm or
if Quick Arm was used to arm system. This code is disabled if
programming mode is exited by the
98 command. Default= 4-1-2-O.
O1 Master Security Code
Enter the 4-digit master security code. Use of a 9 in last position inhibits the
(0000-9999)
Duress feature. This code can assign seconda~ codes for users 03-70.
Default =1-2-3-4. See fields
15, *29, 15O & 1*54 for related security code
options. Note: Do not select the same code for Master Code and Installer Code.
O2 Response Type For
(00-10; see Field *05).
Zones 1-8
*O3 Response Type For
(00-10; see Field *05)
Zones 9-16
*O4 Response Type For
(00-10; see Field 05)
Zones 17-24
O5 Response Type For
Enter the 2-digit zone response type using the numerical codes listed below. If
Zones 25-27
zone 7 is to be used for keyswitch Arm/Disarm operation,
enter 10 as its
(00-1 o)
response type. For protection zones 28-64 and RF Receiver zones 88-91, see
fields 1*01-1
O5& 1*08-109.
The following is a lid of the available response types:
00= Assignfor unusedzones
06= 24-HOUR SILENT
01 = ENTRY/EXIT #1
07= 24-HOUR AUDIBLE
02= ENTRY/EXIT #2
08= 24-HOUR AUXILIARY
03= PERIMETER
09= FIRE
04= INTERIOR, FOLLOWER
10= INTERIOR, DELAY
05= DAY/NIGHT
~08 Not Used
*O9 Entry Delay #1
Enter the entry delay time (01 -15 times 15 seconds or 00 for no delay), up to a
(01-15)
maximum delay of 225 seconds (entry 15 times 15 seconds),
for the zone
assigned to Entry Delay #1. Default = 02. See fields
87 & 145 for entry/exit
sounds options.
1O Exit Delay #1
Enter the exit delay time (01-15 times 15 seconds or 00 for no delay), up to a
(01-15)
maximum delay of 225 seconds, for the zone assigned to Exit Delay #1.
Default = 03.
*11 Entry Delay #2
Enter the entry delay time (01 -15 times 15 seconds or 00 for no delay), up to a
(01-15)
maximum delay of 225 seconds (entry
15 times 15 seconds), for the zone
assigned to Entry Delay #2. This
delay must be longer than Entry ~e/ay #l.
Default = 06.
12 Exit Delay #2
Enter the exit delay time (01-15 times 15 seconds or 00 for no delay), up to a
(01-15)
maximum delay of 225 seconds, for the zone assigned to Exit Delay #2. Note
that this delay must be longer than Exit Delay #1. Default= 08.
—47—