23–1
SECTION 23
Testing the System
••••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
Test Procedure
••••••••••••••••••••••••••••••••••••••••••••••••••
Test Procedure
After installation is completed, the security system should be carefully tested, as follows:
1. With the system in the disarmed state, check that all zones are intact. If a
NOT
READY
(fixed-word keypads) or
DISARMED – Press
to show faults
(alpha keypads) message
is displayed, press [
] to display the faulted zone(s). Restore faulted zone(s) if necessary,
so that the
READY
message (fixed-word keypads) or
DISARMED READY TO ARM
(alpha keypads) is displayed. Fault and restore every sensor individually to assure that it
is being monitored by the system.
2. Enter the 4-digit security code and press the [5] TEST
key. The outside sounder will
sound for 1 second. The keypad should sound 3 beeps each time a contact is faulted. A
"Test"
report should be transmitted (if programmed) to the Central Station immediately.
If the backup battery is discharged or missing, the sounder may not turn on and a
"Low
Battery"
report is transmitted with a
"Test"
report. The keypad beeps periodically as a
reminder that the system is in the Test mode. To turn off the Test mode, enter 4-digit
Security code and press the [1] OFF key.
NOTE:
Arming the panel automatically restores the Test mode, and sends restore and
closing reports to the Central Station (if the reporting has been enabled).
Alarm messages are sent to the Central Station during tests 3 and 4, below. Notify
Central Station personnel in advance that tests will be in progress.
3. Arm the system and fault one or more zones. After 15 seconds (if Optional Dialer Delay is
selected), silence alarm sounder(s) by entering the
Security code
and pressing the [1]
OFF key. Check entry/exit delay zones.
4. Check the keypad-initiated alarms that are in the system by pressing the PANIC key (key
pairs on some keypads). If the system has been programmed for audible emergency, the
keypad emits a
steady
alarm sound, and
ALARM
and zone number is displayed. Silence
the alarm by entering the
Security code
and pressing [1] OFF key.
If the system has been programmed for Silent Emergency, there are no audible alarms or
displays, but a report is sent to the Central Station.
5. If output Relay Units/Powerline Carrier devices have been installed, test their
programmed action.
6 Notify Central Station personnel when all tests are finished, and verify results with them.
7. To test the wireless part of the system and the RF receiver, perform the following two
additional tests:
a.
TRANSMITTER SNIFFER MODE
Make
sure
the system is disarmed before trying to enter this mode.