35
System Programming — Group 7 Comms Options 2
Group 7 — Option 1 Dual Reporting
This option can be programmed in one of two modes:
0. Single Report
1. Dual Report
This option defaults to 0 (Single report).
0 Single Report
If set to 0, event/alarm reporting operates in Single Report mode. The panel has to
communicate with either the primary or secondary telephone number for successful
communication.
When reporting, the panel will dial the Primary Telephone Number:
The panel receives a confirmation signal if successful and the communicator shuts
down until another report needs to be sent. If unsuccessful (i.e. the panel does not
receive a confirmation signal) the panel will try the Secondary Telephone Number.
If the panel does not communicate successfully when dialling the Secondary Tel-
ephone Number, it alternates between each number until it either:
• Communicates with one successfully and receives a confirmation signal.
• Tries each number a total of five times.
Note: A Comms Fail will be given, indicated by a flashing telephone LED ( ) on
the keypad. The communicator will shut down until another report needs sent.
1 Dual Report
If set to 1, the alarm reports in Dual mode, i.e. the panel has to communicate success-
fully with both primary and secondary telephone numbers.
The communicator shuts down until another report needs to be sent if both reports
have been successfully sent.
If either, or both reports are not successful the panel redials the unsuccessful
number(s) until:
• It has successfully reported to both numbers.
• It has tried the unsuccessful number(s) a total of five times. A Comms Fail is
given and the communicator shuts down until another report needs to be sent.
Note: Communication failure is indicated by a flashing telephone LED ( ) on the
keypad.