VISTA-128B Installation Instructions
23-28
Choices for Start/Stop Zone Types:Choices for Start/Stop System Operation:
00 = No Response (Not Used)
01 = Entry/Exit #1
02 = Entry/exit #2
03 = Perimeter
04 = Interior Follower
05 = Trouble Day/Alarm Night
06 = 24-Hr. Silent
07 = 24-Hr. Audible
08 = 24-Hr. Auxiliary
09 = Fire Alarm or Trouble
10 = Interior W/Delay
16 = Fire With Verification
17 = Fire Waterflow
23 = No Alarm Response
(for output relay activation, such
as for access control purposes)
27 = Access Point
(allows more than one relay to be
controlled by activation if access
point request)
18 = Fire Supervisory
19 = 24-Hr. Trouble
20 = Arming-STAY
21 = Arming-AWAY
22 = Disarming ([Code] + Off)
30 = On Second Off
31 = End of Exit Time
32 = Start of Entry Time
33 = Any Burglary Alarm
34 = Code + [#] + 71 Key Entry
35 = Code + [#] + 72 Key Entry
36 = At Bell Timeout **
37 = 2 Times Bell Timeout**
38 = Chime
39 = Fire Alarm
40 = Bypassing
41 = AC Power Fail
42 = System Battery Low
43 = Communication failure
44 = RF Low Battery
45 = Polling Loop Failure
51 = RF Receiver Failure
52 = Kissoff
54 = Fire Zone Reset
55 = Disarm + 1 Minute
56 = XX Minutes (enter XX in field 1*74
stop condition only)
57 = YY Seconds (enter YY in field 1*75
stop condition only)
58 = Duress
60 = Audio Alarm Verification (must
be selected for both START
and STOP operation)
** Or at Disarming, whichever occurs
earlier
If using options 57 and/or 58 (usually as the STOP Zone Type), data fields 1*74 and 1*75 for the
respective relay timeouts for minutes and seconds must be programmed.
02 START: ACS PT
(00-31) 00
If the start zone type selected was 27 (access point), this prompt
will be displayed. Enter the access point
(00-31)
which will
start the relay action.
02 START PART
If the starting event will be limited to occurring on a specific
partition, enter the partition number (
1-8
) in which the start
event will occur. Enter
0
for any partition.
Press [
] to continue.
02 STOP: ZN LIST
NO LIST
If a zone list is being used to stop this relay action, enter the
zone list number
1-8
. The
restore
of a zone on the Zone List
will stop the relay. If a zone list is not being used, enter
0
.
Press [
] to continue.
02 STOP: ZN TYP
If a Zone Type/System Operation is being used to stop
the relay action, enter the 2-digit code as listed in the
Choices for Start/Stop System Operation chart.
Press [
] to continue.
02 STOP: ACS PT
(00-31) 00
If the stop zone type selected was 27 (access point), this prompt
will be displayed. Enter the access point
(00-31)
which will stop
the relay action.