VISTA-128B Installation Instructions
23-26
2) ZONE TYPE/SYSTEM OPERATION (ZT). If all zones to be used to
start the device have the same response type, and there are no other
zones of this type which are not to activate this device, then “ZONE
TYPE” may be used instead of using a "ZONE LIST" and "EVENT” to
activate the device.
If a System Operation, such as “DISARMING” or “ANY FIRE
ALARM,” is to activate the device, the appropriate choice would also
be entered under the “ZONE TYPE” option.
The “ZONE TYPE/SYSTEM OPERATION” option functions
independently of the “EVENT/ZONE LIST” combination.
If a specific "ZONE TYPE" is chosen, any zone of that response type
going into alarm, trouble, or fault will cause the device to activate as
selected in "ACTION.” If the same “ZONE TYPE” is also chosen for the
STOP programming, any zone of that type that restores will de-
activate the device.
If a "SYSTEM OPERATION" is chosen, that operation will cause the
device to activate as selected in "ACTION.” The different choices for
"ZONE TYPE" and "SYSTEM OPERATION" are listed in
“Programming Relays” later in this section, and on the Programming
Form.
3) PARTITION No. (P). The device's "Start" ZONE TYPE/SYSTEM
OPERATION may be limited to an occurrence on one partition (1-8), or
any partition (0).
STOP (STP):
The "STOP" programming determines when and under what conditions
the device will be de-activated. The following options are available:
1). RESTORE ZONE LIST (ZL). If a "ZONE LIST" is used as the “Stop”
event, the device will de-activate when all the zones in that list restore
from a previous fault, trouble, or alarm condition. This will occur
regardless of what is programmed to "START" the device; therefore, a
"RESTORE ZONE LIST" would normally only be used when a "ZONE
LIST" is used to start the device.
2). ZONE TYPE/SYSTEM OPERATION (ZT). Instead of using a
"RESTORE ZONE LIST," a specific zone (response) type or system
operation action can be selected to de-activate the device.
If a specific "ZONE TYPE" is chosen, any zone of that response type
that restores from a previous alarm, trouble, or fault condition will
cause the device to de-activate.
If a "SYSTEM OPERATION" is chosen, that operation will cause the
device to de-activate. The different choices for "ZONE TYPE" and
"SYSTEM OPERATION" are listed in “Programming Relays” later in
this section, and in the Programming Form.
3) PARTITION No. (P). The device's "Stop" Zone Type/System
Operation may be limited to an occurrence on one partition (1-8), or on
any partition (0).
The “ZONE TYPE/SYSTEM OPERATION” option functions
independently of the “EVENT/ZONE LIST” combination.