Section 18 – Final Power-Up Procedure
18-3
Programming Power and AC Options
1. With at least one alpha keypad (6139) wired and properly addressed, power up the
system.
2.
Enter Data Field Programming Mode: [Installer Code] + 8 0 0 0.
Program the following data fields:
*17 AC POWER LOSS KEYPAD SOUNDING (1=yes; 0=no)
*19 AC RANDOMIZE (1=randomize; 0=no)
*28 POWER UP IN PREVIOUS STATE (1=yes; 0=no)
3. Exit Program Mode by entering *99.
If you need more information about actual programming procedures, see The Mechanics of
Programming section.
Total Control Panel Load Worksheets
To calculate the total current for the Auxiliary Power, Alarm Output and polling loop
current, multiply the each device's standby and/or alarm current by the number of units
used.
Polling Loop Current Draw Worksheet
Refer to the POLLING LOOP section for device restrictions for fire and burglary usage.
RPM DEVICE CURRENT # OF UNITS TOTAL
4194 Contact 1mA
4192SD Photo Smoke 0.4 mA
4192SDT Smoke w/Heat 0.4 mA
4192CP Ion Smoke 0.4 mA
4275 Dual PIR 1 .0mA
4278 Quad PIR 1.0 mA
4190 2-Zone RPM 1 mA (LOW);
4190 2-Zone RPM 2 mA (HIGH)
4208 8-Zone RPM 16 mA
4191SN Recessed Contact 1.0 mA
4939SN Surface Mount
Contact
1.0 mA
TOTAL
Cannot exceed 128MA
*
* The total current cannot exceed 128mA. If total load exceeds 128mA, then a 4297 loop
Extender Module can be used. This module is powered from the panel's auxiliary power, and
provides a separate polling loop output, which can support an additional 128mA load. Note
that the total number of points connected to the panel cannot exceed 119.