VISTA-128BP/VISTA-250BP Installation and Setup Guide
A-2
UL611/UL1610 Central Station Burglary Alarm
Follow the instructions for UL609 Local installations given above.
For Grade A Service:
You must use the VISTA-128BP/VISTA-250BP’ dialer with a 7720 Long Range Radio.
Connect the control’s burglary/audible panic alarm trigger (on J7 header) and the 659EN’s phone line monitor
output to the 7720. The 7720 will send a report to the central station when a telephone line fault condition is
detected.
Also connect the 7720’s radio fault output to one of the VISTA-128BP/VISTA-250BP’ EOLR-supervised zones (i.e.,
1-8). Program this zone for a trouble by day/alarm by night (type 05) or a 24-hour alarm (type 07, 08) response to
radio faults.
Program the control’s dialer to send Burglary Alarm, Trouble, Opening/Closing, and Low Battery reports.
For Grade AA Service:
Follow the instructions for Grade A service, except use the 7920SE in place of the 7720.
California State Fire Marshal (CSFM) and UL Residential Fire Battery Backup
Requirements
The California State Fire Marshal and UL have regulations that require all residential fire alarm control panels to
have backup battery with sufficient capacity to operate the panel and its attached peripheral devices for 24 hours in
the intended standby condition, followed by at least 4 minutes in the intended fire alarm signaling condition.
The VISTA-128BP/VISTA-250BP can meet this requirement without using a supplemental power supply, provided
that the panel’s outputs (including the current drawn from the auxiliary power output terminals) are limited as shown
below:
Output current is limited to 750mA maximum total auxiliary power, polling loop, and bell output current.
Maximum auxiliary current is 300mA (including polling loop current).
A 14AH battery is used. (Yuasa model NP7-12 recommended; use two connected in parallel.) A dual-battery
harness is provided with ADEMCO No. 4100EOLR Resistor Kit (kit also contains EOL resistors having spade
lug/heat shrink tubing construction approved by UL and CSFM for fire zone usage). Both batteries fit inside the
panel’s cabinet.