1*57 5800 RF BUTTON GLOBAL ARM [0]
1=enable; 0=disable
1*58 5800 RF BUTTON FORCE ARM [0]
Enter "1" to enable. If a zone is faulted after pressing button,
keypad will beep once. Pressing the button again within 4
sec. bypasses the zone. Enter "0" to disable.
Must be "0" for UL installations.
1*60 ZONE 5 AUDIO ALARM VERIFICATION [0]
Enter 1 If 2-way audio (AAV) is being used; Enter 0 if it is
not.
Must be "0" for UL installations.
1*69 PRINTER TYPE [0]
Enter 0 if you are using a parallel printer connected to the
VA8201 Alpha Pager Module.
Enter 1 if you are using a serial printer.
1*70 EVENT LOG TYPES
[1 0 0 0 1]
Alarm
Chk
Byp
O/C
Syst
1=enable; 0=disable
1*71 12/24 HOUR TIME STAMP FORMAT [0]
0=12 hour; 1=24 hour
1*72 EVENT LOG PRINTER ON-LINE [0]
0=disable; 1=enable
1*73 PRINTER BAUD RATE [0]
1=300; 0=1200
Must be 1200 if using pager interface.
1*74 RELAY TIMEOUT XXX MINUTES [000] | |
Enter the relay timeout, 0-127 in multiples of 2 minutes,
desired for #80 Menu Mode time-driven event relay
command numbers "04/09" and #93 Menu Mode Output
Programming output command "56."
1*75 RELAY TIMEOUT YYY SECONDS [000] | |
Enter the relay timeout, 0-127 seconds, desired for #80
Menu
Mode time driven event relay command numbers "05/10"
and #93 Menu Mode Output Programming command "57."
1*76 ACCESS CONTROL RELAY [00] |
Relay will be pulsed for 2 seconds whenever code + [0] is
pressed. Enter 00-96; 00=none.
Must be "00" for UL.
3rd Page Programming Fields (press *94)
2*00
NUMBER OF PARTITIONS [1]
Enter 1-8
2*01 DAYLIGHT SAVING TIME [04, 10] | |
START/END MONTH Start End
00-12; if no daylight saving time, enter 00,00
2*02 DAYLIGHT SAVING TIME [1, 5] |
START/END WEEKEND Start | End
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last;
6=next to last; 7=3rd from last [1,5]
2*05 AUTO-ARM DELAY [15] |
Enter the time between the end of the arming window and
the start of auto-arming warning period, in values of 1-14
times 4 minutes 00=instant; [15=no auto arm at all]. When
this delay expires, the Auto-Arm Warning Period begins.
2*06 AUTO-ARM WARNING PERIOD [15] |
This is the time during which the user is warned to exit the
premises prior to the auto-arming of the system (beeps every
15 seconds; "ALERT" displayed). Enter 01-15 minutes.
00=instant at end of arming delay.
2*07 AUTO-DISARM DELAY [15] |
This is the time between the end of the disarming window
and the start of auto-disarming. Enter 01-14 times 4 minutes;
00=instant at end of window; 15=no auto-disarm.
2*08 ENABLE FORCE ARM FOR AUTO-ARM [0]
0=disable; 1=enable
2*09 OPEN/CLOSE REPORTS BY EXCEPTION [0]
1=enable; 0=disable
If enabled, only openings and closings occurring outside the
scheduled opening/closing windows will trigger dialer
reports. Opening reports will also be suppressed during the
closing window, in order to prevent false reports when the
user arms the system and then reenters the premises to
retrieve a forgotten item.
2*10 ALLOW DISARMING ONLY DURING [0]
ARMING/DISARMING WINDOWS
0=disable; 1=enable
See system-wide field 2*11 if enabling field 2*10. This
feature adds high security to the installation.
2*11 ALLOW DISARM OUTSIDE WINDOW [0]
IF ALARM OCCURS
Used only if field 2*10 (partition-specific field) is set to "1." If
this field is enabled ("1") the system can be disarmed outside
the disarm window if an alarm has occurred. If "0," disarming
can only be done during the disarm window. If field 2*10 is
set to "0" for a partition, this field has no effect for that
partition.
2*18 ENABLE GOTO FOR THIS PARTITION [0]
1=Allow log-on from other partitions; 0=disable
2*19 USE PARTITION DESCRIPTORS [0]
0=disable; 1=enable
2*20 ENABLE J7 TRIGGERS FOR PARTITION [1]
0=disable for displayed partition; 1=enable for displayed
partition
2*21 ENABLE SUPERVISION PULSES FOR LRR
TRIGGER OUTPUTS [000]
| |
Used for supervised connection to 7920SE. F B P
Enter 0 to disable or 1 to enable the listed outputs.
F= Fire; B= Burglary; P= Silent Panic/Duress.
Must be 1 for UL. Installations.
2*22 DISPLAY FIRE ALARMS OF [0]
OTHER PARTITIONS
0=No; 1=Yes.
2*23 DISPLAY BURG & PANIC ALARMS OF [0]
OTHER PARTITIONS
0=No; 1=Yes.
2*24 DISPLAY TROUBLES OF OTHER [0]
PARTITIONS
0=No; 1=Yes