– 14 –
Programming With #93 Menu Mode
NOTE: The following field should be preset before beginning: 2*00 Number of Partitions. In addition, receivers should
be programmed via Device programming.
After programming all system related programming fields in the usual way, press #93 while still in programming mode to
display the first choice of the menu driven programming functions. Press 0 (NO) or 1 (YES) in response to the displayed menu
selection. Pressing 0 will display the next choice in sequence.
NOTE: All references in this manual for number of zones, number of user codes, number of access cards, and the
event log capacity, use the VISTA-250BP’s features. See page 2 of this manual for the table listing the differences
between the VISTA-128BP and the VISTA-250BP control panels.
U
L
For UL installations, verify that the audio alarm verification feature is disabled.
#93 MENU MODE KEY COMMANDS
The following is a list of commands used while in the menu mode.
#93 Enters Menu mode
[✱] Serves as ENTER key. Press to have keypad accept entry.
[#] Backs up to previous screen.
0 Press to answer NO
1 Press to answer YES
001-009 All data entries are either 2-digit or 3-digit entries.
000 Exits menu mode, back into field programming mode, when entered at the first question for each category.
Menu selections are as follows:
PROMPT
EXPLANATION
ZONE PROG?
1 = YES 0 = NO 0
For programming the following:
• Zone Number
• Zone Response Type
• Partition Number for Zone
• Dialer report code for zone
• Input Device Type for zone (whether RF, polling loop, etc.)
• Enrolling serial numbers of 5800 Series transmitters & serial polling loop devices into the system.
• Zone Attributes (e.g., Arm w/Fault, Silent, etc.)
EXPERT MODE?
1 = YES 0 = NO 0
Same as Zone Programming except:
• Done with a minimum number of keystrokes.
• Can program wireless keys using pre-defined templates.
NOTE: Some of the zone attributes cannot be programmed in the Expert Mode, only in Zone Programming.
REPORT CODE PROG?
1 = YES 0 = NO 0
For programming the following:
• Alarm report codes for zones
• Restore & supervisory codes
• All other system report codes
ALPHA PROG?
1 = YES 0 = NO 0
For entering alpha descriptors for the following:
• Zone Descriptors
• Installer's Message
• Custom Words
• Partition Descriptors
• Relay Descriptors
DEVICE PROG?
1 = YES 0 = NO 0
For defining the following device characteristics for addressable devices, including keypads, RF receivers
(5881), output relay modules (4204/4204CF), FSA modules, 4285/4286 VIP Module, ECP Long Range Radio
(7820), Panel Link module, and VISTA gateway module:
• Device Address
• Device Type
• Keypad Options (incl. partition assignment)
• RF House ID
• LRR Options (incl. programming radio)
• Panel Linking Options
Kommentare zu diesen Handbüchern