89 EVENT LOG 80% FULL REPORT CODE 0 | 0
If an Event Logging selection is made in field
*
90, a message can be sent
to the central station receiver when the log is 80% full. If the log becomes
full, a new message will overwrite the oldest message in the log. NOTE:
Aside from the selection made by the installer in field
*
90, all control and
readout from the log is accomplished via the Downloader.
*
90 EVENT LOGGING 3
0 = No event logging
1 = log Alarm/Alarm Restore
2 = log Trouble/Trouble Restore
4 = log Bypass/Bypass Restore
8 = log Open/Close
x = log combination of events (add value of entries)
Example:
To select
“Alarm/Alarm Restore”, and “Open/Close”, enter 9 (1 + 8); to select
all events , enter #15.
The default of “3” = alarm/alarm restore (1) plus trouble/trouble restore (2).
The VISTA-20HWSE system has the ability to record various events in a
history log (48-event capacity). The types of events to be logged can be
selected as indicated. At any time, the downloader operator can then
upload the log and view or print out all or selected categories of the log.
The log can also be cleared by the downloader operator.
The display/printout at the central station will show the date, time, event,
and description of the occurrences. The time is calculated by an internal
clock at the central station computer. Note that the time for any events
that occur prior to a system power-down or an entry into the programming
mode cannot be calculated by the central station computer. The time will
then appear on the log as “unknown”.
NOTE: System messages are logged when any non-zero selection is
made.
*
91 OPTION SELECTION (Audio Alarm Verification) 0
0 = not using AAV
4 = an Audio Alarm Verification (AAV) unit is connected to the system
UL installations: must be 0 (AAV disabled)
*
92 PHONE LINE MONITOR ENABLE 0
0 = Not used
1 = Local keypad display only when phone line is faulted
2 = Local keypad display plus keypad trouble sound when line is faulted
Each partition turns off its own trouble sound. No automatic timeout.
3 = Same as “2” above plus Device No. 2 STARTS. If either partition is
armed, external sounder activates. External sounder will be turned
off by normal bell timeout, or by security code plus OFF from either
partition (it does not have to be the one that was armed).
NOTE: Option 3 may be used even if a relay unit or Powerline carrier
device is not connected to the control.
Device number 2 must either be programmed to be STOPPED in
field
*
80 or STOPPED by entry of security code + [#] + 8 + 2.
Partition in
*
80 should be set to “0 “for STOP.
NOTE: This feature will not function properly unless the designated earth
ground terminal (25) is connected to an earth ground. If it is not, you may get
false line cut indications.
*
93 NUMBER OF REPORTS IN ARMED PERIOD 0
0 = reports limited to a total of 10
1 = unlimited number of reports
This option can be used to limit the number of messages (alarm & alarm
restore reports) sent to the central station in an armed period.
UL installations: must be 1 (unlimited reports)