*47 SECONDARY FORMAT [0]
0=Low Speed; 1=Contact ID; 2=Ademco High Speed;
3=Ademco Express
*48 LOW SPEED FORMAT (Sec.) [0]
0=Ademco Low Speed; 1=Sescoa/Radionics
*49 CHECKSUM VERIFICATION [0] [0]
1=yes; 0=no Prim Sec
*50 SESCOA/RADIONICS SELECT [0]
1=Sescoa; 0=Radionics
*51 DUAL REPORTING [0]
1=yes; 0=no If used with Spilt Reporting "1" option (1*34), alarms
and alarm restores go to both primary & secondary numbers, while
all other reports go to secondary only. If used with Split Reporting
"2" option, alarms and alarm restores go to both, open/close and
test messages go to secondary only, while all other reports go to
primary. If used with Split Reporting "3" option, fire alarms and fire
supervisory signals go to both primary and secondary , while all
other reports go to secondary only.
*52 STANDARD/EXPANDED REPORT FOR PRIMARY
[0]
Alarm Rstr Bypass Trbl Opn/Cls Low Bat
0=standard; 1=expanded; Note: Expanded overrides 4+2 format.
*53 STANDARD/EXPANDED REPORT FOR SECONDARY
[0]
Alarm Rstr Bypass Trbl Opn/Cls Low Bat
0=standard; 1=expanded; Note: Expanded overrides 4+2 format.
ZONE TYPE RESTORE ENABLES
*79 FOR ZONE TYPES 1-8 *80 FOR TYPES 9/10
12 34 56 7 8 910
1=enable; [0=disable]
*83 FIRST TEST REPORT TIME | | |
[Day 00; hour 12; min 00] Days 01-07 Hours 00-23 Min 00-59;
00 in all boxes=instant (Day 01= Monday)
*84 SWINGER SUPPRESSION [15] |
01-15 alarms; Must be "00" (disabled) for UL.
*85 ENABLE DIALER REPORTS [0]
FOR PANICS & DURESS 995 996 999 Duress
1=enable; 0=disable
*87 ENTRY WARNING [1]
1=continuous; 0=3 beeps
*88 BURG. ALARM COMM. DELAY [0] |
1=16 seconds; 0=no delay. Must be "0" for UL Commercial Burg.
installations.
*89 RESTORE REPORT TIMING [0]
0=Instant; 1=After bell timeout if zone is restored; 2=when system
is disarmed. Must be "0" for fire or UL Commercial Burg.
*90 SEC. SUBS. ACCT # | | | |
Enter 00-09; B-F (11-15) [15 15 15 15]
1*17 LOBBY PARTITION [0]
Enter the "common lobby" partition (1-8)
1*18 AFFECTS LOBBY [0]
Enter 1 if this partition affects the common lobby;
enter 0 if it does not. Must be "0" for Commercial Fire & UL
installations.
1*19 ARMS LOBBY [0]
Enter 1 if arming this partition attempts to arm lobby;
enter 0 if it does not. Must be "0" for Commercial Fire & UL
installations.
1*20 EXIT ERROR LOGIC [0]
0=No, 1=Bypass E/E and Interior zones faulted after
exit delay. Must be "0" for Commercial Fire & UL installations.
1*21 EXIT DELAY RESET [0]
0=No; 1=Resets Exit Delay to 60 seconds after
zone is closed.
Must be "0" for Commercial Fire & UL
installations.
FIELDS 1*22-1*25: Allow four sets of two zones each to be
linked so that both must fault within a five minute period to
cause an alarm.
1*22 CROSS-ZONING PAIR ONE | | | |
1*23 CROSS-ZONING PAIR TWO | | | |
1*24 CROSS-ZONING PAIR THREE | | | |
1*25 CROSS-ZONING PAIR FOUR | | | |
MISCELLANEOUS WIRELESS OPTIONS
Fields 1*28 - 1*32 are not applicable to Commercial
Fire or UL installations.
1*28 RF TX LOW BATTERY SOUND [0]
1=immediate; 0=when disarmed;
1*29 RF TX LOW BATTERY REPORT ENABLE [0]
1=enable; 0=disable
1*30 RF RCVR CHECK-IN INTERVAL [06] |
02-15 times 2 hours; 00 disables supervision
1*31 RF TRANSMITTER CHECK-IN INTERVAL [12] |
02-15 times 2 hours; 00 disables transmitter supervision
1*32 RF RECEIVER TYPE [0]
1=4281; 2=5881
1*33 TOUCH-TONE W/ROTARY BACKUP [0]
1=enable; 0=disable
1*34 COMM. SPLIT REPORT SELECTION [0]
0=no; 1=alarms and alarm restores primary, others
secondary; 2=open/close, test secondary, others primary; 3 =
fire alarms & troubles primary, all secondary. See 51 for
comments if using with dual reporting.
1*42 CALL WAITING DEFEAT [0]
1=Yes; 0=No.
1*43 PERM. KEYPAD BACKLIGHT [0]
1=enable; 0=disable When disabled, display lights when any
key is pressed, and turns off after period of keypad inactivity.
1*44 WIRELESS KEYPAD [0]
TAMPER DETECT ENABLE 1=enable; 0=disable. Must
be "0" for Commercial Fire and UL installations.
1*45 EXIT DELAY SOUNDING [0]
1=enable; 0=disable Produces quick beeping during exit delay
if enabled.
1*47 CHIME ON BELL 1 [0]
1=enable; 0=disable
1*48 WIRELESS KEYPAD ASSIGNMENT [0]
0=disable; enter partition in which RF keypad used, 1-8. Must
be "0" for Commercial Fire and UL installations.
1*49 SUPPRESS TX SUPERVISION SOUND [1]
1=disable; 0=enable. Must
be "0" for Commercial Fire and UL installations.
1*52 SEND CANCEL IF ALARM + OFF [0]
1=no restriction; 0=within bell timeout period only