– 10 –
VISTA 100 MULTIPLE PARTITION PROGRAMMING FORM
Some fields are programmed for each partition (shown as shaded fields). See the PARTITION-SPECIFIC section for
programming these fields. Standard default (*97) values are shown in brackets [ ], otherwise default = 0.
*00 INSTALLER CODE | | |
Enter 4 digits, 0-9 [5140]
*08 TEMPORAL SIREN PULSE [0]
1 = Yes; 0 = No
*09 ENTRY DELAY #1 Partition-Specific
*10 EXIT DELAY #1 Partition-Specific
*11 ENTRY DELAY #2 Partition-Specific
*12 EXIT DELAY #2 Partition-Specific
*13 BELL 1 TIMEOUT Partition-Specific
*15 KEYSWITCH ASSIGNMENT [0]
Enter partition in which keyswitch used,
1-8; 9=Silences bells if fire alarm
present; 0=disable
*16 BELL 1 CONFIRMATION Partition-Specific
OF ARMING DING
*17 AC LOSS KEYPAD SOUNDING [0]
1=yes; 0=no
*18 BELL 1 AC POWER LOSS ALARM [0]
1=yes; 0=no. Must be "1" for UL Commercial Burglary.
*19 RANDOMIZE AC LOSS REPORT [0]
1=randomize 10-40 min.; 2=4-6 hrs; 0=when AC loss
occurs. Must be "2" for Central Station and Remote
Station fire alarm system.
*20 VIP MODULE PHONE CODE | |
Enter 01 - 09 for the first digit; enter [00] , [00]
11 for "
*
" or 12 for "#" for the second digit. Must be
"00, 00] for Commercial Fire & UL Commercial Burg.
installations.
*22 KEYPAD PANIC ENABLES Partition-Specific
*23 MULTIPLE ALARMS Partition-Specific
*24 IGNORE EXPANSION ZONE TAMPER [0]
1=Ignore; 0=Enable tamper for RF and RPMs. Must be
0 for UL if these devices are used.
*25 BURG.TRIGGER FOR RESPONSE TYPE 8 [1]
1=enable; 0=disable
*26 INTELLIGENT TEST REPORTING [0]
1=yes, (no report sent if any other report was
recently sent); 0=no. Must be "0" for Commercial Fire
& UL Commercial Burglary installations.
*27 TEST REPORT INTERVAL [024] | |
Enter interval in hours, 001-999; 000=no report ; Max.
024 for Commercial Fire & UL.
*28 POWER UP IN PREVIOUS STATE [1]
1=yes; 0=no; "1" for UL.
*29 QUICK ARM Partition-Specific
*30 MAIN DIALER (TOUCHTONE OR ROTARY) [0]
1=TouchTone; 0=rotary
*31 PABX ACCESS CODE | | | |
00-09; B-F (11-15)
*32 PRIM. SUBS. ACCT # Partition-Specific
*33 PRIMARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause.
*34 SECONDARY PHONE NUMBER
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause.
*35 DOWNLOAD PHONE No.
Enter 0-9 for each digit. Enter #11 for *, #12 for #,
#13 for 2 second pause.
*36 DOWNLOAD ID No.
|
| | | | | | |
Enter 00-09; A-F (10-15) [15 15 15 15 15 15 15 15]
*37 DOWNLOAD COMMAND ENABLES
0
Dialer System Not Remote Remote Remote Upload Download
Shutdwn Shutdwn Used Bypass Disarm Arm Program Program
See field 1*53 for Callback disable option; [1=enable];
0=disable; For Commercial Fire & UL installations, all
options must be disabled.
*38 PREVENT ZONE XXX BYPASS Partition-Specific
*39 OPEN/CLOSE REPORT Partition-Specific
FOR INSTALLER
*40 OPEN/CLOSE REPORT FOR KEYSWITCH [0]
1=enable; 0=disable
*
41 NORMALLY CLOSED or EOLR (Zones 3-8) [1]
1=N.C.loops; 0=EOLR supervision; Must be "0" for
Commercial Fire & UL.
*42 DIAL TONE PAUSE [0]
0=5 seconds; 1=11 seconds; 2=30 seconds; Must be
"0" for Commercial Fire & UL.
*43 DIAL TONE DETECTION [1]
1=wait for true dial tone; 0=pause, then dial
*44 RING DETECTION COUNT [00]
|
01-14; 15=answering machine; 00=no detection. Must
be "0" for Commercial Fire & UL Burglary.
*45 PRIMARY FORMAT [0]
0=Low Speed; 1=Contact ID; 2=Ademco High Speed;
3=Ademco Express
*46 LOW SPEED FORMAT (Primary) [0]
0=Ademco Low Speed; 1=Sescoa/Radionics
*47 SECONDARY FORMAT [0]
0=Low Speed; 1=Contact ID; 2=Ademco High Speed;
3=Ademco Express
*48 LOW SPEED FORMAT (Sec.) [0]
0=Ademco Low Speed; 1=Sescoa/Radionics
*49 CHECKSUM VERIFICATION [0] [0]
1=yes; 0=no PrimScndry
*50 SESCOA/RADIONICS SELECT [0]
1=Sescoa; 0=Radionics
Seitenansicht 9