- 8 -
Updated: 8/17/12
Tech Note
Total Load (ma @ 11.5) Vdc
22 ga
20 ga
18 ga
16 ga
1-16
6,000
6,000
6,000
6,000
17-24
4,850
6,000
6,000
6,000
25-32
3,640
5,850
6,000
6,000
33-40
2,910
4,680
6,000
6,000
41-48
2,420
3,900
6,000
6,000
49-56
2,080
3,350
5,290
6,000
57-64
1,820
2,930
4,630
6,000
65-72
1,620
2,600
4,110
6,000
73-80
1,450
2,340
3,700
5,880
81-88
1,320
2,130
3,370
5,350
89-96
1,210
1,950
3,090
4,900
197-104
1,120
1,800
2,850
4,520
105-112
1,040
1,670
2,650
4,200
113-120
970
1,560
2,470
3,920
121-128
910
1,460
2,310
3,680
Table 2: Polling Loop Wiring Using Shielded (or metal conduit) one side of the shield to ground.
Wiring Notes and Recomendations
Twisted, stranded, non-shielded cable is recommended. Avoid sharp bends in the wire.
Shielded cable, running Aux power in the same jacket, and/or running wire in metallic conduit increase the
capacitance of the wire run, which limits distances.
Observe device and control requirements on serial number vs. dip-switch mode.
Avoid running the cable near keypad wiring, intercom, or AC power lines, anything emitting RF noise.
If the V/Plex device will go serial the device has to be programmed as serial.
Shielded wire should have one end of the shield to good Earth Ground.