Tech Note
Check 97/997 (polling loop short)
Indicates that there is a physical short or Low Voltage on the polling loop, or too much current being drawn.
1. The panel recognizes a short when the voltage on the polling loop drops to 4.5 Vdc or below.
2. Isolate this by checking voltage on the polling loop with wires connected and with all wires removed.
Check troubleshooting section under
Random Checks.
Limitations of V-plex Cable runs
The ADEMCO Polling Loop (V-plex) has t he foll owi ng li mi t at i ons, which apply to panels with 128ma
Procedure for Determining the Maximum Wire Length per Polling Loop
:
1. Use table 1A for Unshielded Twisted cable and table 1B for Shielded cable.
2. Determine the maximum device loading on the polling loop branch by adding the load currents per device
determined from
Table 2.
a. Example: One 4190SN requires 2.0 mA. One 4208U requires 27.3 mA. The total load for one
4208U plus five 4190SNs on the same loop would be (27.3+ 10.0) = 37.3 ma.
3. Locate the row in the table selected in step 1 corresponding to the total device load current determined in
step 2. Example: A total load current of 37.3 mA, corresponds to the row of (33-40) mA.
4. The maximum cable length can now be determined from the size, or gauge, of the wire used in the cable.
5. Example: The maximum cable length of No. 20 gauge wire for a total device load of 37.3 mA is 4,680 ft if
either unshielded (table 1A) cable or shielded (table 1B) cable is used. If No. 18 gauge wire were used
instead, the maximum allowable cable length would be 7,410 ft for unshielded cable and 6,000 ft for
shielded cable.
Total Load (ma @ 11.5) Vdc
22 ga
18 ga
16 ga
1-16
12,000
12,000
12,000
17-24
4,850
12,000
12,000
25-32
3,640
9,260
12,000
33-40
2,910
7,410
11,760
41-48
2,420
6,170
9,800
49-56
2,080
5,290
8,400
57-64
1,820
4,630
7,350
65-72
1,620
4,110
6,540
73-80
1,450
3,700
5,880
81-88
1,320
3,370
5,350
89-96
1,210
3,090
4,900
197-104
1,120
2,850
4,520
105-112
1,040
2,650
4,200
113-120
970
2,470
3,920
121-128
910
2,310
3,680
Table 1: Polling Loop Wiring Using Unshielded Twisted (or non-metal conduit)