Tech Note
Ground Fault Troubleshooting (Applies to Commercial Fire Panels
Only)
Troubleshooting
1. Measure Volts DC between terminals 12 (Panel Negative) and terminal 30 (Ground)
(Note: KP (-), zone (-) and polling loop (-) are all common. Any of these may be used. The exception to
this is any zone that supports 2-wire smoke detectors, and the bell circuits.)
2. To determine where the ground fault is coming from, remove system wires until the voltage between
terminal 12 and 30 returns to 1VDC. Note: as you remove each wire, leave it off until the problem is
corrected. There may be more than one wire with a problem. Note: Leave the earth ground wire connected
during this process.
3. As this progresses, you may eventually reach a point where all wires are removed except the battery and
the earth ground. The next step is to remove the panel from the cabinet. Lay the PCB on a non conductive
material (wood or cardboard). With the earth ground wire now disconnected the panel should give you
1VDC from terminal 12 to 30. If not, the panel is defective.
Notes
Under normal conditions (no ground faults) you should read 1.0VDC (+ or - .5VDC)
A ground fault is sensed when some external input causes the voltage between terminal 12 (Panel Negative) and
terminal 30 (ground) to either drop below .5 VDC or increase above 1.5 VDC