Using Multiple 4297 Polling Loop Extenders
L
E
L
= Total wire length on output side of each 4297.
P
=
L
Total wire length on input side of each 4297.
E1
+
(L
P1
+ L
P2 +
…
L
PN +
L
PE
) ≤
12,000 ft., unshielded; ≤
L
6,000 ft., shielded
E2 +
(L
P1
+ L
P2
+…
L
PN + LPE
) ≤
12,000 ft., unshielded; ≤
L
6,000 ft., shielded
En
+ (L
P1
+ L
P2 +
…
L
PN + LPE
) ≤
12,000 ft., unshielded; ≤
6,000 ft., shielded
Note:
The maximum number of 4297 modules which can be connected in parallel to a single system control is limited to
no more than 8, and by the maximum wire lengths specified above and the need for the Aux or Local power source
to supply 50 ma per 4297. For example, if five 4297 modules are used, the Aux or Local power source must supply
(5) (50) = 250 ma and the total system load current would be (5)(128)+128 = 768 ma, max. Also, from the above
relations;
If (L
P1
+ L
P2 +
…
L
PN +
L
PE
) = 1000 ft., then L
E1
= L
E2
=… L
En
≤ 5,000 ft., shielded.
≤ 11,000 ft., unshielded
Panel Polling
Loop Output
Control
Power Source
(50 ma per
Extender)
P1
P2
PN
E1
E2
EN
Refer to Table 2 for maximum L
E1
wire length per wire size , wire type, and total unit loads.
Refer to Table 2 for maximum L
E2
wire length per wire size , wire type, and total unit loads.
Refer to Table 2 for maximum L
EN
wire length per wire size , wire type, and total unit loads.
Refer to Table 2 for maximum L
PE
wire length per wire size , wire type, and total unit loads.
PE
Figure 2: Using Multiple 4297's