VISTA-50P/VISTA-50PUL Installation and Setup Guide
3-7
++
-
N.C.
N.C.
N.O.
2k EOLR 2k EOLR
+-
++
-
N.C.
N.C.
2k EOLR 2k EOLR
++
-
N.C.
+
+
-
N.C.
N.C.
2k EOLR
SMOKE
Zone resistance (Excluding EOLR):
ZONE 1,8: 100 OHMS MAXIMUM
ALL OTHER ZONES: 300 OHMS MAXIMUM
ZONE 1
ZONE 2 ZONE 3 ZONE 4 ZONE 5 ZONE 6 ZONE 7 ZONE 8 ZONE 9
2-WIRE SMOKE
DETECTOR LOOP
(Also supports NO/NC Burg contacts)
Programmable Response
(Fast/Normal) Loop
LATCHING TYPE GLASS
BREAK DETECTORS
10 11 12 13 14 15 16 17 18 19 20 21 22 23
N.C.
N.O.
N.O. N.O.
2k EOLR
N.O. N.O.
N.O.
N.C.
N.O.
2k EOLR
2k EOLR
N.C.
GLASS
BREAK
Fire
Usage
Burg.
Usage
Red Jumper
Zone response time:
ZONES 1-8: 350mSec-500mSec
ZONE 9: Programmable for
Fast: 10mSec-15mSec
Normal: 350mSec-500mSec
(default response)
hw_zones-001-V0
Figure 3-9: Wiring Connections for Zones 1-9
Using 2-Wire Smoke Detectors on Zone 1
Zone 1 can support up to 16 2-wire smoke detectors.
The alarm current on zone 1 supports only one
smoke detector in the alarmed state.
Compatible 2-Wire Smoke Detectors
DETECTOR TYPE DEVICE MODEL #
Photoelectric, direct-wire System Sensor 2400
Photoelectric w/heat sensor, direct-wire System Sensor 2400TH
Photoelectric w/B401B base System Sensor 2451
Photoelectric w/heat sensor & B401B System Sensor 2451TH
Ionization, direct-wire System Sensor 1400
Ionization w/B401B base System Sensor 1451
Photoelectric duct detect (DH400 base) System Sensor 2451
Photoelectric duct detect (DH400 base) System Sensor 2451
Ionization duct detector (DH400 base) System Sensor 1451DH
Ionization, direct-wire System Sensor 1100
Ionization w/B110LP base System Sensor 1151
Photoelectric, direct-wire System Sensor 2100
Photoelectric w/heat sensor, direct-wire System Sensor 2100T
Photoelectric w/B110LP base System Sensor 2151
U
L
These smoke detectors are UL Listed for use
with the VISTA-50P/VISTA-50PUL and are
the only 2-wire smoke detectors that may be
used.
Wiring 2-Wire Smoke Detectors to Zone 1
2K EOL resistors must be used on fire zones
and must be connected across the loop wires
of each zone at the last detector.
To wire 2-wire smoke detectors to zone 1, perform the
following steps:
Step Action
1 Select up to 16 2-wire smoke detectors from
the list of compatible detectors.
2 Connect 2-wire smoke detectors across zone 1
terminals (10 and 11) as shown in Figure 3-
10. Observe proper polarity when connecting
the detectors.
3 Connect the EOL resistor at the last detector
in the loop across the zone 1 terminals. The
EOL resistor must be connected across
the loop wires at the last detector.
2k EOLR
ZONE 1
SMOKE
(+)
(-)
2-WIRE SMOKE
DETECTOR
10
11
(+)
(-)
Figure 3-10: 2-Wire Smoke Detector on Zone 1