VISTA-250FBP (3/17/2003) 13850 - 9
Detection and Alarm
(2) Sescoa/Radionics.
(3) ADEMCO Express.
(4) ADEMCO High Speed.
(5) ADEMCO Contact ID.
b. Backup reporting – The system shall support backup reporting via
the following:
(1) Secondary phone number.
(2) ECP long-range radio (LRR) interface.
(3) Option to select long range radio (LRR) or dialup as the
primary reporting method (dynamic signaling feature).
c. Internet reporting – The system shall be capable of communicating
with the central station via the internet using Alarmnet-i. It shall
provide the user with the ability to control the system via a browser
interface (i.e., AOL, Netscape, Internet Explorer). All packet data
transmitted to the monitoring station shall be encrypted with a
minimum of 1024 bits of encryption.
20. Audio Alarm Verification Option - Provides a programmable Audio
Alarm Verification (AAV) option that can be used in conjunction with an
output relay to permit voice dialog between an operator at the central
station and a person at the premises.
21. Cross-Zoning Capability - Helps prevent false alarms by preventing a zone
from going into alarm unless its cross-zone is also faulted within 5
minutes.
22. Pager Interface – The Control Panel shall be capable of sending event
information to an alphanumeric pager via a pager interface device.
23. 24-Volt Power Supply – The Control Panel shall be compatible with a 24-
Volt power supply module. The module shall supply two (2) 24 vdc, 3.4
amps, rectified, unfiltered outputs, which power:
a. Alarm notification appliances, including but not limited to sirens
horns, bells and strobes.
b. Auxiliary devices capable of operating using full-wave rectified
unfiltered voltage.
24. Exit Error False Alarm Prevention Feature – The System shall be capable
of differentiating between an actual alarm and an alarm caused by leaving
an entry/exit door open. If not subsequently disarmed, the control panel
shall: