ADDENDUM TO: INSTALLATION INSTRUCTIONS FOR 5140XM CONTROL
USE WITH ISSUE: N6019V1
RE: Feature Changes and New Program Fields
This addendum applies to 5140XM Controls which are shipped with firmware EPROM
marked:
WA5140XM-XX (where XX = 18 or higher)
The EPROM is located beneath the main PC board shield cover.
The following features are new for the 5140XM Control.
1. In accordance with revisions to UL864, Standard for Commercial Fire Alarms, the following
system changes have been made.
Silencing Console Sounds for Fire Supervisory Zone Type now requires security code + OFF
To silence console sounds triggered by supervisory conditions on zones programmed for fire zone
supervisory response (zone response type 18), you must enter the security code + OFF. Prior to this
change, these console sounds could be silenced by pressing any key (no security code was needed).
Keyswitch Mode 2 Operation (field *15)
New fire or burglary alarm conditions occurring after a previous alarm was silenced using the
keyswitch will now automatically re-activate the corresponding fire or burglary alarm bell circuits when
keyswitch mode 2 operation is selected (field *15 set to 2). Prior to this change, alarm bell circuits
remained silenced until the security code + OFF was entered at a console.
Note that when keyswitch mode 2 operation is selected, operating the keyswitch will silence fire and
burglary alarms only when a fire alarm condition is present (in accordance with the existing
Installation Instructions).
OFF-NORMAL Communicator Test Report (new program fields 3*53, 3*54)
Off-normal conditions are fire alarm system related conditions existing at the time a normal test report
is sent. These conditions include fire alarms, fire troubles or supervisories, and certain system
troubles such as earth ground faults, AC failure, low system battery, or bell circuit faults. The 5140XM
now transmits an "off-normal" communicator test report (programmed in field 3*53, 3*54) instead of
the normal communicator test report (programmed in fields *81, *82) when fire alarm system off-
normal conditions are present at the time of test report transmission.
As shipped, both reports are disabled and must be enabled for installations that provide fire alarm
central station service. The normal communicator test report is enabled as described in the
Installation Instructions. The off-normal communicator test report is enabled as follows:
Field 3*53 Field 3*54
First Digit Second Digit
| |
For Ademco High Speed and Ademco Contact ID report formats: Enter "01" in field 3*53.
Ademco High Speed off-normal test reports use channel 3 =1 and status channel = 9
Contact ID sends code 608.
For Low Speed Formats: Enter the first (event code) digit of the report in field 3*53 and the second
(zone number) digit of the report in field 3*54. These fields require that two numbers be entered for
each digit of the report (i.e. enter 00 if no digit is to be sent, enter 01 for "1", enter 10 for "A"..., enter
15 for "F").
Note: fields 3*53 and 3*54 can also be programmed by loading one of the four built-in communication
defaults as follows:
Communicator Default 3*53 Value 3*54 Value
Low Speed (*94*80) 05 00
Ademco Express (*94*81) 15 00
Ademco High Speed (*94*82) 01 00
Ademco Contact ID (*94*83) 01 00