Section 1 - General Description
1-xiii
Individually assignable to bell outputs and/or aux. relay
U
L
Wireless devices are not permitted in UL Commercial Burglary installations. UL Listing of the
5808 Smoke Detector for Commercial Fire installations is pending
.
For specific information regarding the number of wireless zones supported by each RF receiver,
see
Section 8:
Wireless Expansion
.
Supervisory Zones
Provides additional zones for supervision of all peripheral devices such as keypads, RF
receivers, and relay modules, as well as for system zones (bells, dialers (telephone lines),
earth ground, keypad panics, etc.) and individual relays. Zone assignments are as follows:
Individual Relay Zones 601-616
Peripheral Device Zones 800-831
System Zones 970-999
(See Section 20: Zone Index for a full explanation of these zones and specific zone
assignments.)
Maintenance Signal Support
The control monitors maintenance signals from certain smoke detectors (5805, 4192CPM,
4192SDM, 4192SDTM). Maintenance signals are triggered when a smoke detector gets
dirty, and indicate that the detector should be cleaned or replaced. If a detector maintains a
high- or low-sensitivity condition for longer than 24 hours, the control sends a dialer report
(trouble message for non-Contact ID reports; Event Code 385 or 386 for Contact ID reports),
makes an event log entry, and displays HSENSxxx or LSENSxxx at the keypads (xxx = zone
number).
NOTE: 5808 Wireless Smoke Detectors report high sensitivity regardless of whether the
condition is actually high sensitivity or low sensitivity.
8 Partitions
Provides the ability to control 8 separate areas independently, each functioning as if it had
its own separate control. Partitioning features include:
A "Common Lobby" partition (1-8), which can be programmed to arm automatically when
the last partition that shares the common lobby is armed; and programmed to disarm
when the first partition that shares the common lobby is disarmed
A Master Partition (9), used strictly to assign keypads for the purpose of viewing the
status of all 8 partitions at the same time (master keypads)
All zones (except fire) are assignable to one of 8 partitions
Fire zones must be assigned to Partition 1
Keypads are assignable to one of 8 partitions or to Master Partition 9, to view system
status
Ability to assign relays to one or all 8 partitions
Ability to display fire and/or burglary and panic and/or trouble conditions at all other
partitions’ keypads (a selectable option)