29-1
SECTION 29
Testing The System
••••••••••••••••••••••••••••••••••••••••••••••••
In This Section
♦
Checkout Procedure for Hardwired Zones
♦
Checkout Procedure for Polling Loop Zones
♦
Checkout Procedure for Wireless Zones
♦
Battery Test
♦
Dialer Test
♦
Fire Drill Test
♦
One-Man Fire Walk-Test
♦
Burglary Walk-Test
♦
Armed Burglary System Test
♦
Trouble Conditions
♦
Turning the System Over to the User
♦
To the Installer
••••••••••••••••••••••••••••••••••••••••••••••••
Checkout Procedure for Hardwired Zones
After installation of all hardwired zones is complete, you should check each partition of the
security system as follows:
1. Make certain that none of the devices or sensors connected to the hardwired zones is in a
faulted state. Doors and windows with contacts should be closed, and PIRs should be
covered (use a cloth to mask them temporarily, if necessary).
2. With all hardwired zones intact, the alpha keypads connected to the system should
display:
DISARMED
READY TO ARM.
If the following is displayed,
DISARMED Press
✴
to show faults
press
✴
to display the faulted zone(s).
Restore any faulted zone(s) as necessary (also make sure that you have connected a 2000-
ohm EOL resistor across the terminals of unused zones). When the keypad displays
“DISARMED...READY TO ARM,” you can proceed to the next step.
3. Fault and then restore each contact or sensor on each zone individually to verify that it is
being monitored by the system. Each time you fault a zone, the keypads in the partition