1*73 PRINTER BAUD RATE 1=300; 0=1200 [0]
1*74 RELAY TIMEOUT XX MINUTES [000] | |
Enter the relay timeout, 0-127 in multiples of 2 minutes, desired
for #80 Menu Mode time driven event relay command numbers
"04/09" and #93 Menu Mode Relay Programming output
command "56".
1*75 RELAY TIMEOUT YY SECONDS [000] | |
Enter the relay timeout, 0-127 seconds, desired for #80 Menu
Mode time driven event relay command numbers "05/10" and
#93 Menu Mode Relay Programming command "57".
1*76 ACCESS CONTROL RELAY Partition-Specific
FOR PARTITION
3rd Page Programming Fields (press *94)
2*00 NUMBER OF PARTITIONS [1]
Enter 1-8
2*01 DAYLIGHT SAVINGS TIME [04, 10] | |
START/END MONTH Start End
00-12; if no daylight savings time, enter 00,00
2*02 DAYLIGHT SAVINGS TIME [1, 5] |
START/END WEEKEND # Start | End
Enter 1-7. 1=first; 2=second; 3=third; 4=fourth; 5=last; 6=next
to last; 7=3rd from last [1,5; 1st Sunday in April, last in Oct.]
2*05 AUTO-ARM DELAY Partition-Specific
2*06 AUTO-ARM WARNING PERIOD Partition-Specific
2*07 AUTO-DISARM DELAY Partition-Specific
2*08 ENABLE FORCE ARM FOR Partition-Specific
AUTO-ARM
2*09 ENABLE OPEN/CLOSE REPORTS Partition-Specific
BY EXCEPTION
2*10 ALLOW DISARMING ONLY Partition-Specific
DURING ARMING/DISARMING WINDOWS
2*11 ALLOW DISARM OUTSIDE WINDOW [0]
IF ALARM OCCURS
Used only if field 2*10 (partition-specific field) is set to "1". If
this field is enabled ("1") the system can be disarmed outside
the disarm window if an alarm has occurred. If "0", disarming
can only be done during the disarm window. If field 2*10 is set
to "0" for a partition, this field has no effect for that partition.
2*18 ENABLE GOTO FOR THIS Partition-Specific
PARTITION
2*19 USE PARTITION DESCRIPTORS [0]
0=disable; 1=enable
2*20 ENABLE J2 TRIGGERS Partition-Specific
FOR THIS PARTITION
2*21 ENABLE SUPERVISION PULSES FOR LRR
TRIGGER OUTPUTS [000] | |
Used for supervised connection to 7920SE. F B S
Enter 0 to disable or 1 to enable the listed outputs.
F= Fire; B= Burglary; S= Silent panic/duress. Must be "1" for
Commercial Fire & UL.
2*22 DISPLAY FIRE ALARMS OF Partition-Specific
OTHER PARTITIONS
2*23 DISPLAY BURG & PANIC Partition-Specific
ALARMS OF OTHER PARTITIONS
2*24 DISPLAY TROUBLES OF Partition-Specific
OTHER PARTITIONS
4th Page Programming Fields (press *94)
3*00 DISPLAY TRBL INSTEAD OF CHECK [0]
0=Check Displayed; 1=Trbl Displayed
3*13 SUPV. N.O./N.C. SELECTION [0]
0=Supv. on short/trouble on open; 1=supv. on short or open
3*14 WATERFLOW SILENCE OPTION [1]
0=Silence on Code + OFF; 1=Silence when waterflow
restores. This feature may only be set to "1" by permission of
the local authority.
3*15 ALARM BELL SOUND [1,0]
0=pulsed; 1=steady Bell 1 Bell 2
3*16 DELAY for ZONE TYPES 17 & 18 [00] |
(Waterflow & FIre Supv) Enter 00-15 times 2 seconds
3*17 ALTERNATE FUNCTION (TAMPER) [0]
FOR ZONE 6 0=disabled; 1=enabled
3*18 EXTENDED DELAY FOR TYPES 17&18 [0]
3*19 ENABLE J2 HEADER PRINTER PORT [0]
0=pins 5&9 function as per field 3*20; 1=pins 5&9 act as
printer RXD & DTR
3*20 TRIGGER OUTPUTS SELECTION [0]
0= LORRA full connection & Remote Console Sounder;
1=LORRA ilmited conn. & Keyswitch LEDs; 2=LORRA fire
only conn. & 5140LED
3*21 MAX # OF DIALER ATTEMPTS [8]
1-8 (3, 4 or 5 for NFPA72 compliant systems when a secondary
phone number is programmed (field *34)
3*30 DIALER SELECTION [1,0]
1=enabled; 0=disabled Main Backup
3*31 BACKUP DIALER TOUCHTONE/ROTARY [0]
1=TouchTone; 0=Rotary
3*50 ZONE TYPE RESTORE ENABLES
FOR ZONE TYPES 16-18 16 17 18
Must be "1" for Commercial Fire & UL installations.
3*57 BELL 2 & AUX. RELAY Partition-Specific
CONFIRMATION OF ARM DING
3*58 BELL 2 & AUX. RELAY AC POWER
LOSS ALARM 1=yes; [0=no] Bell 2 AUX.Relay
3*59 ENABLE BELL 2 & AUX. RELAY Partition-Specific
CHIME ANNUNCIATION
3*60 BELL 2 & AUX. RELAY TIMEOUT Partition-Specific
3*61 AUX. RELAY FUNCTION [1]
0=Trouble/supervisory; 1=Alarm, silenced by code + OFF
2=Smoke Detector Reset; 3=Battery Save; 4=Alarm, silenced
by code + [#] + 67
3*82 ENABLE BURG. FEATURES ON PART. 1 [1]
1=enable; 0=disable; “0” disables AWAY, STAY, MAX, TEST,
INSTANT & CHIME functions
3*85 ENABLE FIRE & SYSTEM ZONE BYPASS [1]
0=not enabled; 1=only installer can bypass]; 2=only installer
& master user can bypass. Applies to fire zone types 9, 16, 17
& 18 and system zones 70-77. Applies to Partition 1 only.