ADEMCO Vista-32FB Einstellungsanleitung Seite 9

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 128
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 8
ix
UL864 (Commercial Fire) Compliance
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
••
General Information
The VISTA-32FB control panel provides features that allow the system to meet UL864 Commercial
Fire requirements. To meet these requirements, follow the guidelines outlined in this section.
The reporting of bypassed points to the central station must be enabled in Report Code Programming mode.
Fire alarm notification circuits must be supervised (e.g., supervisory zones 970 and 971 for Bell 1 and Bell 2 outputs).
Only one relay of the 4204CF can be programmed for a NAC. If the 4204CF relay is programmed as a NAC, the stop
action must be programmed as a zone type 62, Bell 2 Timeout.
Output devices are not intended for overriding automatic fire and building functions.
Line cut detection must be enabled for both the main and backup phone lines (supervisory zones 974 and 975).
Access Control Devices cannot be used.
Audio Alarm Verification Devices cannot be used.
Remote downloading can only be performed if a service person is at the premises.
All supervision zones for the polling loop, RF receivers, keypads, NAC outputs, and telephone lines that are used, must
be enabled as zone type 19 (24-hour trouble).
Programming Field Settings for UL864 Compliance
NOTICE TO USERS, INSTALLERS, AUTHORITIES HAVING JURISDICTION, AND OTHER
INVOLVED PARTIES
This product incorporates field-programmable software. In order for the product to comply with the requirements
in the Standard for Control Units and Accessories for Fire Alarm Systems, UL 864, certain programming features
or options must be limited to specific values or not used at all as indicated below.
Program feature or option Permitted in
UL864? Y/N
Possible settings Settings permitted in UL 864
08 TEMPORAL SIREN
PULSE
N 0 = disable
1 = enable
Not used at this time. Must
be set to “0” (disable).
13 ALARM SOUNDER
(BELL) TIMEOUT
Y Enter 01-15 multiplied by 2
minutes. 00 = no timeout.
Must be set to “3” (Minimum
of 6 minutes).
17 AC LOSS KEYPAD
SOUNDING
N 0 = disable
1 = enable
Must be set to “1” (enabled).
20 VIP MODULE
PHONE CODE
N Enter 01 - 09 for the first
digit; enter11 for “*” or 12 for
“#” for the second digit.
Not used. Must be set to “00”.
22 KEYPAD PANIC
ENABLES (PARTITION
SPECIFIC)
N 0 = disable
1 = enable
Must be set to “000” for
partition 1 in fire systems.
23 MULTIPLE
ALARMS (PARTITION
SPECIFIC)
N 0 = disable
1 = enable
Must be set to “1” (enabled).
26 INTELLIGENT
TEST REPORTING
N 0 = disable
1 = enable
Must be set to “0” (disable).
Seitenansicht 8
1 2 3 4 5 6 7 8 9 10 11 12 13 14 ... 127 128

Kommentare zu diesen Handbüchern

Keine Kommentare