Section 3 - Installing the Control
3-9
+
-
-
+
-
+
EOL
POWER
SUPERVISION
RELAY
MODULE
EOLR-1
4-WIRE SMOKE
DETECTORS
2000
OHM
EOLR
HEAT
DETECTOR
+
BLK
+
-
ZONE
TERMINALS
(15-27)
12
11
10
9
N.O.
POLE
N.C.
Aux. Pwr 1
CONTROL
P
ANEL
SHOWN POWERED.
RELAY OPENS WHEN
POWER IS LOST
AUXILIARY RELAY
8
7
+
Keypad Prt 1
4_wiresmk-005-V0
Figure 3-9: Wiring Auxiliary Relay for Smoke Detector Reset
Telephone Line Connections
The VISTA-128FBP/VISTA-250FBP provides one main built-in dialer for communication to the central station and one
optional 5140DLM Backup Dialer, both supervised for voltage and current on the phone lines.
Do not connect the system to telephone lines that require ground start service.
U
L
For Listed fire central station (UL864/NFPA 72) applications, use communications device 7845i-ent alone, the
main dialer with the
7845i-ent or use the main dialer with the 5140DLM.
For listed fire remote station (UL864/NFPA 72) applications, use the main dialer with the 5140DLM.
Telephone line supervision is required for commercial fire alarm systems.
Main Dialer Connections
To connect the main dialer, refer to the Summary of Connections diagram and perform the following steps:
Step Action
1 Connect the main dialer to the telephone company lines using the RJ31X cable supplied.
2 If the dialer output is connected to telephone lines that have a telephone company MTU installed, cut the
blue jumper (W6).
Installing the 5140DLM Backup Dialer
Do not connect the main dialer and the backup dialer to the same telephone company line.
To install the 5140DLM, refer to the Summary of Connections diagram and perform the following steps:
Step Action
1 Mount the 5140DLM to the main PC board shield.
2 Connect the backup dialer to the telephone company lines using the RJ31X cable supplied.
3 Connect the backup dialer to the J3 connector on the main PC board using the ribbon cable (supplied with
the module).
4 Connect the earth ground screw on the 5140DLM to the earth ground terminal (30) on the main PC board
using 16AWG wire.
5 If the dialer output is connected to telephone lines that have a telephone company MTU installed, cut the
blue jumper on the 5140DLM PC board.
Telephone Line Supervision
If the tip/ring voltage falls below approximately 25 volts (13 volts if the blue jumper is cut) or the handset current is less
than approximately 10mA, the supervision circuits for the dialer output will indicate a fault condition. Faults on the
phone lines are displayed as zones 974 (main dialer) and 975 (backup dialer).
To prevent risk of shock, disconnect the phone lines at the telco jack before servicing the panel.
If the communicator is connected to a telephone line inside a PABX, be sure the PABX has backup power
supply that can support the PABX for 24 hours (central station usage) or 60 hours (remote station usage).
Many PABXs are not power-backed up, and connection to such a PABX results in a communication failure if